Download Goodman Furnace GMH95/GCH95/GME95/GCH9 Diagnostic LED Error Code

Written by 

Find Your Goodman Furnace GMH95/GCH95/GME95/GCH9 Diagnostic and error LED Code here.

Goodman GMH95/GCH95/GME95/GCH9 furnace provides a LED on its integrated furnace control for quick diagnostic. Here is its diagnostic code error codes:

\

GMH95/GCH95/GME95/GCH9
GAS-FIRED WARM AIR FURNACE

 

TROUBLESHOOTING CHART

Symptoms of Abnormal Associated Fault Description(s) Possible Causes Corrective Action Cautions and Notes

Operation LED Code2

• Furnace fails to operate.

• Integrated control module diagnostic LED provides no signal.

NONE

• No 115 volt power to furnace, or no 24 volt power to integrated control module.

• Blown fuse or circuit breaker.

• Integrated control module has an internal fault.

• Manual disconnect switch

OFF, door switch open, or

24 volt wires improperly connected or loose.

• Blown fuse or circuit breaker.

• Integrated control module has an internal fault.

• Assure 115 and 24 volt power to furnace integrated control module.

• Check integrated control module fuse (3A). Replace if necessary.

• Check for possible shorts in 115 and 24 volt circuits. Repair as necessary.

• Replace bad integrated control module.

• Turn power OFF

prior to repair.

• Replace integrated control module fuse with 3A automotive fuse.

• Read precautions in “Electrostatic Discharge” section of manual.

• LED is Steady On.

ON

CONTINUOUS ON

• Normal Operation

•Normal Operation

• None

•Normal Operation

• Furnace fails to operate.

• Integrated control module diagnostic LED is

flashing ONE (1) flash.

1

1 FLASH

• Furnace lockout due to an excessive number of ignition “retries” (3 total)1.

• Failure to establish flame. Cause may be no gas to burners, front cover pressure switch stuck open, bad igniter or igniter

alignment, improper orifices,

or coated/oxidized or improperly connected flame sensor.

• Loss of flame after establish- ment. Cause may be interrupted gas supply, lazy burner flames (improper gas pressure or restriction in flue and/or combustion air

piping), front cover pressure

switch opening, or improper induced draft blower performance.

• Locate and correct gas interruption.

• Check front cover pressure switch operation (hose, wiring, contact operation). Correct if necessary.

• Replace or realign igniter.

• Check flame sense signal. Sand sensor if coated and/or oxidized.

• Check flue piping for blockage, proper length, elbows, and termination.

• Verify proper induced draft blower perfor- mance.

• Turn power OFF prior to repair.

• Igniter is fragile, handle with care.

• Sand flame sensor with emery cloth.

• See “Vent/Flue Pipe” section for piping details.

• Furnace fails to operate.

• Integrated control module diagnostic LED is

flashing TWO (2) flashes.

2

2 FLASHES

• Pressure switch circuit is closed.

• Induced draft blower is not operating.

• Induced draft blower pressure switch contacts sticking.

• Shorts in pressure switch circuit.

• Replace induced draft blower pressure switch.

• Repair short.

• Turn power OFF

prior to repair.

• Replace pressure switch with proper replacement part.

• Induced draft blower runs continuously with no further furnace operation.

• Integrated control module diagnostic LED is

flashing THREE (3)

flashes.

3

3 FLASHES

• Pressure switch circuit not closed.

• Induced draft blower

is operating.

• Pressure switch hose blocked, pinched or connected improperly.

• Blocked flue and/or inlet air pipe, blocked drain system, or weak induced draft blower.

• Incorrect pressure switch setpoint or malfunctioning switch contacts.

• Loose or improperly connected wiring.

• Inspect pressure switch hose. Repair, if necessary,

• Inspect flue and/or inlet air piping for blockage, proper length, elbows, and termination. Check drain system. Correct as necessary.

• Correct pressure switch setpoint or contact motion.

• Tighten or correct wiring connection.

• Turn power OFF prior to repair.

• Replace pressure switch with proper replacement part.



1 Integrated control module will automatically attempt to reset from lockout after one hour.

2 LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.

If you feel that you have benefited from this site, and would like to show your appreciation, you can throw a buck or two in the Tip Jar - Thank you!

TROUBLESHOOTING CHART

Symptoms of Abnormal Associated Fault Description(s) Possible Causes Corrective Action Cautions and Notes

Operation LED Code2

• Circulator blower runs continuously. No furnace operation.

• Integrated control module diagnostic LED is

flashing FOUR (4)

flashes.

4

4 FLASHES

• Primary or auxiliary limit circuit is open.

• Insufficient conditioned air over the heat exchanger. Blocked filters, restrictive ductwork, improper circulator blower speed, or failed circulator blower.

• Faulty primary or auxiliary limit switch.

• Loose or improperly connected wiring.

• Check primary/ auxiliary limit. Replace if necessary.

• Check filters and ductwork for block- age. Clean filters or remove obstruction.

• Check circulator blower speed and performance. Correct speed or replace blower if necessary.

• Tighten or correct wiring connection.

• Turn power OFF

prior to repair.

• Replace primary/ auxiliary switch with proper replacement part.

• Replace blower with correct replacement part.

• Induced draft blower, and circulator blower runs continuously. No furnace operation.

• Integrated control module diagnostic LED is

flashing FIVE (5) flashes.

5

5 FLASHES

• Flame sensed with no call for heat.

• Short to ground in flame sense circuit.

• Correct short at flame sensor or in flame sensor wiring.

• Turn power OFF

prior to repair.

• Circulator blower runs continuously. No furnace operation.

• Integrated control module diagnostic LED is

flashing SIX (6) flashes.

No furnace operation.

6

6 FLASHES

• Rollout limit circuit is open.

Integrated control module fuse is

blown.

• Flame rollout.

• Misaligned burners, blocked flue and/or air inlet pipe, or failed induced draft blower.

• Loose or improperly connected wiring.

• Faulty rollout limit.

• Short in 24 volt AC control circuits or safety circuits.

• Check burners for proper alignment.

• Check flue and air inlet piping for blockage, proper length, elbows, and termination. Correct as necessary.

• Check induced draft blower for proper performance. Replace, if necessary.

• Tighten or correct wiring connection.

• Repair short in 24 volt AC control/safety circuit(s)

• Replace integrated control module fuse (3A).

• Turn power OFF

prior to repair.

• See “Vent/Flue Pipe” section for piping details.

• Replace rollout limit with correct replacement part.

• Replace induced draft blower with correct replace- ment part.

• Replace integrated

control module fuse with 3A automotive fuse.

• Read precautions in “Electrostatic Discharge” section of manual

• Normal furnace operation.

• Integrated control module diagnostic LED is flashing SEVEN (7) flashes.

7

7 FLASHES

• Flame sense microamp signal is low.

• Flame sensor is coated/

oxidized.

• Flame sensor incorrectly positioned in burner flame.

• Lazy burner flame due to improper gas pressure or combustion air.

• Sand flame sensor if coated/oxidized.

• Inspect for proper sensor alignment.

• Check inlet air piping for blockage, proper length, elbows, and termination.

• Compare current gas pressure to rating plate info. Adjust as needed.

• Turn power OFF

prior to repair.

• Sand flame sensor with emery clot.

• See “Vent/Flue Pipe” section for piping details.

• See rating plate for proper gas pressure.

• Furnace fails to operate.

• Integrated control module diagnostic LED is flashing continu- ously.

C

CONTINUOUS/ RAPID FLASH

• Polarity of 115 or 24 volt power is reversed.

• Polarity of 115 volt AC power to furnace or integrated control module is reversed.

• Orange and gray wires to transformer are reversed.

• Poor unit ground.

• Review wiring diagram to correct polarity.

• Reverse orange and gray wires connected to transformer.

• Verify proper ground. Correct if necessary.

• Turn power OFF

prior to repair.

2 LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.

Find Goodman GMH95/GCH95/GME95/GCH9 Service Facts for troubleshooting flow chart. Uploading Shortly

Read 137 times
SBE Electric Heating Cooling

At SBE you find quality service at affordable rates. SBE is here to service all of your electric, heating, air conditioning, and refrigeration needs.

Website: sbeelectricandhvac.com

Related items

1 comment

  • Comment Link Paul A. Sunday, 19 February 2012 00:18 posted by Paul A.

    Thanks for your posting. Very informative, helped me narrow down to a dirty flame sensor. :-)

Leave a comment

Make sure you enter the (*) required information where indicated.\nBasic HTML code is allowed.

Testimonials

This was my Facebook Status... Anyone needing heating, air conditioning, or electrical service, call Rich. He just installed a new heating/air conditioning unit in my house and did a fantastic job at a reasonable price. His number is 267-480-7080. Highly recommended!
Izzy C.
Swarthmore,PA


Thank you for fixing our AC the birds thank you as well. Showed up late at night and in 10 minutes found a bad part and had the system working again. Thank You
Lenny B.
Lansdale,PA

Save With High Efficiency AC Heat and Tankless Hot Water

trane products 300x175 Noritz-Tankless-Water-Heaters

Live Support Chat